Hub van Doorneweg 8 • 2171 KZ Sassenheim – NL •
T
+31(0)252 228850 •
F
+31(0)252 228235 •
E
I
euronormdrives.com
92
93
NEURN030000_220_A
NEURN030000_220_A
V-9 External analog speed control (External 0 ~ 10V voltage signal given)
V-9-1 Electrical diagram:
Circuit breaker
380V 50/60Hz
Three phase input power supply
Motor
%
M
0
~
+10V DC
(Default)
FWD/STOP
REV/STOP
External simulation speed regulation
(External 0 ~ 10V voltage signal given)
0 ~ 10V Analog signal
V-9-2 Connection:
The (+) terminal of the external analog signal is connected to the AI1 terminal, and the other terminal of the signal is
connected to the GND terminal of the inverter.
V-9-3 Parameter setting:
No.
Code
Parameter name
Setting
range
F0.03
Frequency source master setting
AI1analog quantity setting
2
F0.11
Command source selection
Terminal block control (LED on)
1
F1.00
DI1 terminal function selection
Forward run (FWD)
1
F1.01
DI2 terminal function selection
Reverse run(REV)
2