Category
Symbol
Name
Function
Digital input
DI1
Multi-function
digital input 1
1.Optocoupler, compatible bipolar input, determined by the choice of the jumper PLC;
2.Input impedance: 3.3kΩ
3.Level input voltage range is 19.2~28.8V.
Note: DI5 input impedance is 1.65k.
DI2
Multi-function
digital input 2
DI3
Multi-function
digital input 3
DI4
Multi-function
digital input 4
DI5
Multi-function
digital input 5
DI6
Multi-function
digital input 6
DI7
Multi-function
digital input 7
DI8
Multi-function
digital input 8
DI5
High-speed
pulse input
terminals
Except the function of DI1~DI4,DI6~DI8,DI5 can also be used as high-speed pulse input
channels. Maximum input frequency: 100kHz
Note: when using high-speed pulse input, it should be connected to PLC and di5 port
respectively.
Analog
output
DA1-GND
Analog output 1
The selected DA1 jumper on control panel determines voltage or current output. Output voltage
range: 0~10V , output current range: 0~20mA
DA2-GND
Analog output 2
The selected DA2 jumper on control panel determines voltage or current output. Output voltage
range: 0~10V , output current range: 0~20mA
Digital out
-
put
SPA-COM
Digital output 1
Opto-coupler isolation, bipolar open collector output
Output voltage range: 0~24V , output current range: 0~50mA
SPB-COM
Digital output 2
SPB-COM
High-speed
pulse output
Subject to function code(F2.00)”SPB terminal output mode selection”
As a high-speed pulse output, the highest frequency up to 100kHz;
Relay out
-
put
TA1-TC1
Normally open
terminals
Contactor drive capacity: Normally closed contact 3A/AC 250V,normally open contact 5 A/AC
250V, COSø = 0.4.
TB1-TC1
Normally closed
terminals
Motor temper
-
atur
e inspec
-
tion input
S1-S2-
GND
PT100 inspect
wire input
PT100 temperature senso. Note: Such as PT100 three detection line, with a universal table test,
to find two of the detection line is 0Ω after the one received S2 terminal, the other received a
GND; the remaining one received S1 terminal.
Built-in
RS485
485+
485 differential
terminal
485 communication interface, 485 differential signal terminal, use twisted-pair or shielded wire
connect to the standard 485 communication interface
485 jump line in the control panel to decide whether to connect the terminal resistance
485-
485 differential
signal - terminal
Auxiliary interface
J13
communication
interface
CAN card, 26-pin terminal
J10
PG card
interface
12-pin terminal
GND
GND ground
interface
GND jump line decide whether to connect PE, improve the inverter anti-interference
COM
COM ground
interface
COM jump line decide whether to connect PE, improve the inverter anti-interference
H1
COM Terminal
interface
Consistent with the COM function on the terminal line.