No.
Fault
ID
Failure type
Possible causes
Solutions
9
Err.09
Under voltage
fault
1. The momentary power cut
2. The inverter’s input voltage is not within the
specification
3. The bus voltage is not normal
4. The rectifier bridge and buffer resistance are
abnormal
5. The drive panel is abnormal.
6. The control panel is abnormal
1. Reset fault
2. Adjust the voltage to the normal range
3. Seek for technical support
10
Err.10
Inverter overload
1. The type selection of inverter is small
2. Whether the load is too large or the motor stall
occurs
1. Choose the inverter with large power level
2. Reduce the load and check the motor and its
mechanical conditions
11
Err.11
Motor Overload
1. Power grid voltage is too low
2. Whether the setting motor protection parameters
(F8.03) is appropriate or not
3. Whether the load is too large or the motor stall
occurs
1. Check the power grid voltage
2. Correctly set this parameter.
3. Reduce the load and check the motor and its
mechanical conditions
12
Err.12
Input phase loss
1. The drive panel is abnormal.
2. The lightning protection plate is abnormal
3. The main control panel is abnormal
4. The three-phase input power is not normal
1. Replace the drive, the power board or contactor
2. Seek for technical support
3. Check and eliminate the existing problems in
the peripheral line
13
Err.13
Output phase
loss
1. The lead wires from the inverter to the motor is not
normal
2. The inverter’s three phase output is unbalanced
when the motor is running
3. The drive panel is abnormal.
4. The module is abnormal
1. Eliminate peripheral faults
2. Check the motor’s three-phase winding is normal
or not and eliminate faults
3. Seek for technical support
14
Err.14
Module
overheating
1. The air duct is blocked
2. The fan is damaged
3. The ambient temperature is too high
4. The module thermistor is damaged
5. The inverter module is damaged
1. Clean up the air duct
2. Replace the fan
3. Decrease the ambient temperature
4. Replace the thermistor
5. Replace the inverter module
15
Err.15
External
equipment fault
Input external fault signal through the multi-function
terminal DI
Reset run
16
Err.16
Communication
fault
1. The communication cable is not normal
2. The settings for communication expansion card
F9.07 are incorrect
3. The settings for communication parameters F9
group are incorrect
4. The host computer is not working properly
1. Check the communication cable
2. Correctly set the communications expansion card
type
3. Correctly set the communication parameters
4. Check the wiring of host computer
17
Err.17
Contactor fault
1. Input phase loss
2. The drive plate and the contact are not normal
1. Check and eliminate the existing problems in
the peripheral line
2. Replace the drive, the power board or contactor
18
Err.18
Current detection
fault
1. Check Hall device
2. The drive panel is abnormal.
1. Replace the drive panel
2. Replace hall device
19
Err.19
Motor parameter
auto tuning fault
1. The motor parameters was not set according to
the nameplate
2. The identification process of parameter is timeout
1. Correctly set motor parameter according to
the nameplate
2. Check the lead wire from the inverter to the motor
20
Err.20
Disk code fault
1. The encoder is damaged
2. PG card is abnormal
3. The encoder model does not match
4. The encoder connection has error
1. Replace the encoder
2. Replace the PG card
3. Correctly set the encoder model according to
the Actual conditions
4. Eliminate the line fault
21
Err.21
EEPROM read
and write fault
EEPROM chip is damaged
Replace the main control panel
22
Err.22
Inverter
hardware fault
1. overvoltage
2. overcurrent
1. Eliminate overvoltage fault
2. Eliminate overcurrent fault
23
Err.23
Short-circuit to
ground fault
Motor short to ground
Replace the cable or motor