6 Start-up
Mycom S CPM 153
38
Hauser
6.5.5
Set up 1 – Relays
To enter the menu, proceed as follows:
⇒
⇒
PARAM
pH
7.00
Param
Parametrieren
Grundeinstellung
Sonderfunktionen
Handbedienung
Quick
Setup
Edit
Weiter E
pH
7.00
Hold
Param
Settings
Set up 1
Set up 2
Manual operation
First start up
Edit
Next
E
pH
7.00
Param
Set up 1
Sensor input
Display
Access codes
Current output
Relays
Edit
Next
E
Hold
CODE
SELECTION
(default = bold)
INFO
F1
NAMUR:
Relay 1:
Relay 2:
Relay 3:
Relay 4:
Relay 5:
off
free
free
free
free
free
Contact functions
Depending on the equipment available, you can assign
the function of up to 5 relays here. The relays 1 and 2 will
be assigned to an activated NAMUR
function and won’t be available for other functions (com-
pare page 14).
Selection:
Free / Controller / LC / CCW / CCC
Controller:
Controller control using relay
LC
: Limit contactor function
CCW
: ChemoClean water. Water supply for the Chemo-
Clean function.
CCC
: ChemoClean Cleaner. Cleaner supply for the
ChemoClean function.
(Together, CCC and CCW form the "ChemoClean" func-
tion. You can find information on ChemoClean on
page 72 )
The limit value/controller relays are configured in the
"PARAM"
➞
"Set up 2"
➞
"Controller confiuration".
!
Note!
•
Danger of data loss.
If you change the relay
allocation
after
configuring the controller and the num-
ber of relays available to the controller is
reduced
, the
complete
controller settings (s. page 56) is reset to
the default values.
• If you change the relay assignment for the controller,
you must use the controller menu (s. page 56) to reas-
sign all the functions selected there to a relay.
Example
: Relays 4 and 5 are assigned to the
controller and you change the controller assignment to
relays 5 and 6 (number of relays remains 2)
(no data loss, providing the number of assigned relays
is not reduced!).
• You can only activate the NAMUR and ChemoClean
functions, when the required relays 1 and 2 (s.
page 14) are free.