Oil Temperature Setpoints
The
O
IL
T
EMPERATURE
S
ETPOINTS
screen allows the operator to set acceptable ranges for the
RECIP oil temperature.
The following table lists the data entry fields and a description of their purposes.
TERM
DEFINITION
RANGE
HIGH FAILURE
The compressor will be failed (stopped) when
the oil temperature exceeds this value.
32 - 392 DEGF
HIGH ALARM
The Viltech will report an alarm to the operator
when the oil temperature exceeds this value
32 - 392 DEGF
HEATER CONTROL
The temperature at which to maintain the oil in
the separator. The oil heater uses the Oil
Temperature sensor but only when the compressor
is stopped.
32 - 392 DEGF
LOW ALARM
The Viltech will report an alarm to the operator when
the Oil Temperature is below this value.
32 - 392 DEGF
LOW FAILURE
The compressor will be failed (stopped) when the
Oil Temperature is below this value.
32 - 392 DEGF
Oil Temperature Setpoints Screen
Oil Temperature Definitions
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......