Control Group Select
The sequencer control group select screen permits the user to set the control, low alarm, and low
failure setpoints for the different control groups. Below is an example of a sequencer control group
select screen. If the sequencer contains multiple system control parameters, a menu will allow
selection of control groups for each parameter.
The following table lists the various parameters displayed on the sequencer suction pressure control group
select screen. The range of these parameters will vary depending on the type of system control parameter
used.
TERM
DEFINITION
RANGE
CONTROL SETPT
The sequencer will add or remove compressors to
29.9 INHG-
maintain the system control parameter at this
185.3 PSIG
control setpoint.
LOW ALARM
An alarm is activated when the system control
29.9 INHG-
parameter is below this value.
185.3 PSIG
LOW FAILURE
A failure is activated when the system control
29.9 INHG-
parameter is below this value.
185.3 PSIG
Sequencer Control Group Select Definitions
Sequencer Control Group Select Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......