63
TERM
DEFINITION
RANGE
ACTIVE GROUP
There are four possible suction pressure control
groups, each with its own pressure parameters.
This field is used to manually select the active
setpoint group.
S1 -S4
High Suction Pressure Setpoints
The
H
IGH
S
UCTION
P
RESSURE
alarm and failure setpoints are not scheduled and are active
regardless of which group is in control.This screen also has the High Suction Limit & Unloading
for each step of CapacityControl
The following table lists the data entry fields for the High Suction Pressure Set-points screen
TERM
DEFINITION
RANGE
HIGH FAILURE
The compressor is failed (stopped) when this
29.9 INHG
value is exceeded.
-185 PSIG
HIGH ALARM
The Viltech reports an alarm to the operator when
29.9 INHG
this value is exceeded.
-185 PSIG
Suction Pressure Active Group Control Definitions
High Suction Pressure Setpoints Screen
High Suction Pressure Data Definitions
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......