140
No.
Parameter Name
Level
Default Comments
27. High Intermediate Pressure (Two Stage) Alarm 58PSIG
Spare (One Stage)
28. Low Intermediate Pressure (Two Stage) Alarm 45PSIG
Spare (One Stage)
29. Low Intermediate Pressure (Two Stage) Fail 40PSIG
Spare (One Stage)
Discrete Alarms
The Micro checks the state of the
Motor Output and Aux Input. To verify
correct operation Aux contact closed
indicates the motor is running. If
Motor is running when it should be off
the Micro will take the following
steps:(1) Failure signal is generated
to alert operator: (2) Capacity is
forced to a full unload condition.