126
Sequencer Operating Procedures
The sequencer function will use a SEQ hot key to allow the operator to adjust the controls for the various
sequencers contained in the system. The following sections describe the various procedures used in the
sequencer function.
Sequencer Status Screen
The presence of a SEQ hot key will add at least one sequencer status screen to the list of status screens.
The extra status screen appears when the user scrolls through the system status screens. Below is an
example of a sequencer status screen. Multiple sequencer status screens may be present depending on
the systems configuration.
TERM
DEFINITION
SEQUENCE OPERATION
The state of the sequencer (DISABLED, DECREASING, INCREASING,
HOLDING). Also shows the value of the staging timer.
SUCTION PRESS
The current value of the system suction pressure for system process
temperature.
GROUP
Shows the current control group being used.
SETPOINT
The current setpoint value utilized by the sequencer. Engineering units
will change to DEGF if Process Temperature is being used.
LEAD LIST (Status)
Shows the currently selected lead list number and the value of the
standby monitor timer.
LEAD LIST (Heading)
Shows the current order of compressors in the lead list.
COMPRESSOR
Shows the names of the compressors in the lead list.
STATUS
The current sequencer status of the compressors (UNAVAIL, STANDBY,
FULL LOAD, TRIM, HOTSTBY).
MODE
The current mode of each compressor.
STATE
The state of each compressor.
ANTICYCLE
The time remaining on each compressor’s anti-cycle timer.
The following table lists the data entry and information fields on the screen and a description of their purpose.
Sequencer Status Screen Definitions
Sequencer Status Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......