116
Variable Frequency Drive Option
When VFD is enabled, a Proportional-Integral-Derivative (PID) algorithm is used to generate a 4-20mA control
signal to the VFD. The VFD in turn varies the frequency and voltage to the motor resulting in slower or faster
speeds.
The VFD option will only work when the option is enabled and the VFD single channel analog output board
(VPN-3400G) is connected to the microprocessor board. The analog output card is to be placed on the
microprocessor board towards the left-center, by four black “holes” and there is a connector labeled “J5
ANALOG OUTPUT.”
The VFD is enabled by pressing the “Menu” key then press the number 4 for “System Setup” then press
number 5 for “Configure Hardware” and then press number 5 for “Control Configuration”. After enabling the
VFD option, the configuration of the VFD can be located by pressing the “SETPT” key then press number 4
for “Capacity Control” and then press number 2 for “Motor Speed.”
Motor Control Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......