79
The following table lists the data entry and information fields on the screen and a description of their purposes.
TERM
DEFINITION
RANGE
NORMAL
Adjusts the sensitivity of the time proportional control routine.
BANDWIDTH
0 - 20 DEG
CONTROL
The capacity will not be adjusted if the Process Temperature is within
DEADBAND
the control deadband.
0 - 20 DEG
NORMAL
The Normal Stage Delay Timer starts when the Suction Pressure
STAGE DELAY
exceeds the Control Deadband. When it expires, a stage will be added
or removed as appropriate
1 - 999 SEC
FAST STAGE
The Fast Stage Delay Timer starts when the Suction
DELAY
Pressure exceeds the Normal Bandwidth.
1 - 999 SEC
SETPOINT
The current control setpoint group and value (reference).
N/A
PROCESS TEMP
The current Process Temperature value (reference)
N/A
CAPACITY
The current Capacity (reference)
N/A
RECIP MODE
The current compressor mode (reference).
N/A
RECIP STATE
The current compressor state (reference).
N/A
MISC Control
The
MISCELLANEOUS CONTROL
screen provides setpoints and controls for various system parameters.
Process Temp Control Setpoints Definitions
Miscellaneous Control Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......