51
Anti-Cycle Timer
The
A
NTI
-C
YCLE
T
IMER
is used to avoid repeated start attempts within a user programmable period of
time. The Anti-Cycle timer is started with the motor and must completely count down before the motor
can be started again. The duration of the Anti-Cycle timer can be adjusted from the Miscellaneous
Controls.
Power Fail Restart
The operator can define a
P
OWER
F
AIL
R
ESTART
time from the miscellaneous controls screen. If the
Viltech
is reset manually or due to a loss of power the down time is calculated and compared to this
setpoint. If power was off longer than the power fail restart time a failure is reported. If the power loss
was less than the setpoint no failure is reported and the compressor remains on-line and is allowed to
automatically restart if required.
Process Temperature Control (Option)
When the
P
ROCESS
T
EMPERATURE
option is enabled, the RECIP compressor capacity is adjusted to
maintain the outlet temperature of a product or process instead of suction pressure
(e.g. chiller outlet temperature control). The control strategy is documented in the Capacity Control
section above.
Two Stage Configuration (Option)
In a
T
WO
S
TAGE
C
ONFIGURATION
, an intermediate pressure and temperature sensor are monitored. High Failure,
High Alarm, Low Alarm and Low Failure setpoints are provided for each.
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......