17
NOTES:
1) CONNECT ALL SENSOR DRAIN WIRES AT THIS
LOCATION.
2) DOTTED WIRING REPRESENTS FIELD WIRING
3) DOTTED COMPONENTS NOT BY VILTER
4) FOR NEMA 3, 3R, 4 & 12 PANELS, ALL OPENINGS TO
BE GASKETED.
5) MOTOR STARTER WIRING WILL VARY. REFER TO
STARTER MANUFACTURER‘S DIAGRAM FOR ACTUAL
WIRING.
6) ALL CONDUIT CONNECTIONS TO THE PANEL MUST
BE MADE WITH FLEXIBLE CONDUIT.
7) FUSE 5 AMP FAST BLOW.
8) ONLY (4) FOUR INCHES OF SIGNA WIRES SHOULD
BE UNSHIELDED AT SENSOR END.
9) CABLE FOR ANALOG DEVICES UNLESS SHOWN
OTHERWISE IS BELDEN #9533 OR EQUIVALENT. 24
AWG, 3 CONDUCTOR, SHIELDED WITH DRAIN WIRE,
RUN IN SEPARATE CONDUIT FROM POWER WIRING.
MAX WIRE SIZE FOR TERMINAL IS #14AWG. USE
COPPER CONDUCTORS ONLY WITH TEMPERATURE
RATING 60°C OR HIGHER. TIGHTENING TORQUE 4 LB-
IN.
10) MAXIMUM TOTAL SENSOR DRAW IS 2 AMPS. IF
GREATER THAN 2 AMPS IS REQUIRED CUSTOMER
SUPPLIED POWER SUPPLY IS REQUIRED. CONSULT
MANUFACTURER FOR DETAILS.
11) MAX WIRE SIZE FOR I/O BOARD TERMINAL IS
#12AWG. USE COPPER CONDUCTORS ONLY WITH
TEMPERATURE RATING 60°C OR HIGHER. TIGHTEN-
ING TORQUE 4 LB-IN MAXIMUM CURRENT FOR FORM
C RELAY IS 4 AMPS MAXIMUM CURRENT FOR SOLID
STATE OUTPUT MODULE IS 1.5 AMPS.
12) DRAWING IS SHOWN WITH INTERNALLY SUPPLIED
POWER ALTHOUGH IT IS CONFIGURABLE TO CUS-
TOMER SUPPLIED POWER.
13) 120 VAC OUTPUTS MAX. LOAD: 1.5 AM RUNNING,
30 AMPS INRUSH.
14) MAX WIRE SIZE FOR INPUT POWER TERMINAL IS
#10AWG. USE COPPER CONDUCTORS ONLY WITH
TEMPERATURE RATING 60°C OR HIGHER. TIGHTEN-
ING TORQUE 4.4-5.3 LB-IN.
15) CABLE FOR COMMUNICATION BETWEEN PANELS
OR COMPUTER IS BELDEN #9843, OR EQUIVALENT. 24
AWG, 6 CONDUCTOR, TWISTED PAIR SHIELDED WITH
DRAIN WIRE, RUN IN SEPARATE CONDUIT FROM
POWER WIRING.
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......