48
Capacity Ramp Start Limiting
The
C
APACITY
R
AMP
S
TART
feature has been provided to limit capacity increases after the
compressor starts. The operator can define the total time to limit capacity increases from the minimum
capacity to 100% capacity. Once the compressor has started and the minimum capacity has been
achieved, the capacity ramp timer is started, and further capacity increases will be limited. The
maximum allowable capacity will be gradually increased from the minimum capacity to 100% over the
ramp duration. When the capacity is limited due to this feature, the RECIP state will display
“
LIMIT:CAP
”. Unlike other limiting and unloading, the compressor is not considered fully loaded
when in this state.
The Capacity Ramp Start feature is available in Automatic, Auto-Remote and Sequenced mode.
When in Sequenced mode, capacity changes are limited when the compressor is a Fully Loaded
machine. If a fully loaded compressor is forced to unload for any reason, the capacity ramp will
engage from the current capacity position once the limiting condition has gone away. The Capacity
Ramp Start parameters are set-up on the Capacity set-point screen.
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......