129
The following table lists the data entry fields and a description of their purposes. The ranges for these
parameters will vary based on the type of system control parameter used.
PARAMETER
DEFINITION
RANGE
SEQ NORMAL BANDWIDTH
The sequencer load and unload normal
0 - 20 PSID
bandwidth define when normal staging
stops and fast staging begins. If the
difference between the setpoint and
system control parameter is greater than
the bandwidth fast staging is performed.
SEQ CONTROL DEADBAND
The sequencer load and unload control
0 - 20 PSID
deadbands define a zone around the
setpoint where no staging action will be
taken.
SEQ NORMAL STAGE DELAY
The sequencer normal stage delay is
0 - 99 MIN
used to add or remove stages when the
difference between the system control
parameter and the setpoint is outside
the deadband but within the normal
bandwidth. Entering a zero for the load
or unload normal stage delay time
disables staging under these conditions.
SEQ FAST STAGE DELAY
The sequencer fast stage delay is used to
0.1 - 10 MIN
add or remove stages when the difference
between the system control parameter and
the setpoint is outside the normal
bandwidth.
Sequencer Control/Setpoints Screen Definitions
Sequencer Control Setpoints Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......