131
Lead List
The sequencer lead list defines the order that the compressors will be added or removed. The “NONE”
selection is used to allow the operator to remove a compressor from the lead list. The user should make sure
no duplicate entries exist in the lead list and that no two sequencers contain the same compressor at the
same time. Two lead lists are now provided as a standard in most new control systems. Lead List A or B may
be selected manually or scheduled along with the sequencer control setpoint.
The following table lists the various parameters displayed on the sequencers lead list screen.
TERM
DEFINITION
RANGE
LEAD LIST A
The order of compressors in the A lead list.
Selectable
LEAD LIST B
The order of compressors in the B lead list.
Selectable
CURRENT ACTIVE
Allows the user to select the Lead List to be
Selectable
LEAD LIST
used by the sequencer. The new lead list will
effect when the screen is saved.
Sequencer Lead Screen Definitions
Sequencer Lead List Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......