52
The following table lists possible momentary screens associated with the START mode key function.
SCREEN
FUNCTION
STARTING MANUAL MODE
The compressor is starting in the Manual mode.
STARTING AUTOMATIC MODE
The compressor is starting in the Automatic mode.
ON-LINE REMOTE MODE
The compressor is on-line in the Remote mode and may be started by the
remote computer.
ON-LINE AUTO-REMOTE MODE
The compressor is on-line in the Auto-Remote mode and may start,
depending on the state of the Remote Start/Stop input, or the remote
computer.
ON-LINE SEQUENCED MODE
The compressor is on-line in the Sequenced mode and may start,
depending on the master sequencer.
START DISABLED ALREADY
The start function is disabled because the compressor is already in the
IN PROGRESS
process of undergoing the start-up operation.
START DISABLED SYSTEM
The start function is disabled because the compressor is already IS
RUNNING
running.
START DISABLED ANTI-CYCLE
The compressor is delayed from starting. An anti-cycle timer has been
XX:XX
activated which prevents start-up until the time period has expired
(XX:XX is the time remaining). The screen will continue to be displayed
until the timer expires or the user presses the QUIT key.
START DISABLED SYSTEM
The start function is disabled due to a system alarm or ALARM/ failure.
ALARM/FAILURE
Operational Procedures
The operator interface for the RECIP compressor is performed using LCD, keypad, and the
following four hot keys:
STOP
SETPT
LOGS
MENU
The following sections will explain the operating procedures associated with each of these
hot keys.
Momentary Screen
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......