Intermediate Pressure Setpoints (Two Stage only) Option
The
I
NTERMEDIATE
P
RESSURE
S
ETPOINTS
screen allows the operator to set acceptable ranges for the
intermediate pressure, and is only visible on the two stage compressor. An example of the screen is shown below.
The following table lists the data entry fields and a description of their purposes.
TERM
DEFINITION
RANGE
HIGH FAILURE
The compressor is failed (stopped) when the Intermediate
Pressure exceeds this value.
0 - 225 PSIG
HIGH ALARM
The Viltech reports an alarm to the operator when the
Intermediate Pressure exceeds this value.
0 - 225 PSIG
LOW ALARM
The Viltech will report an alarm to the operator when the
Intermediate Pressure is below this value.
0 - 225 PSIG
LOW FAILURE
The compressor will be failed (stopped) when the
Intermediate Pressure is below this value.
0 - 225 PSIG
Intermediate Pressure Setpoints
Intermediate Pressure Definitions
Summary of Contents for Vilter VilTech
Page 1: ...VILTech micro controller Operation and service manual ...
Page 2: ...2 ...
Page 10: ...10 Notes Page ...
Page 11: ...11 ...
Page 16: ...16 ...
Page 18: ...18 ...
Page 29: ...29 ...
Page 38: ...38 ...
Page 53: ...53 ...
Page 88: ...88 ...
Page 138: ...138 ...
Page 142: ...142 ...
Page 145: ...145 ...
Page 147: ...147 ...
Page 153: ...153 ...
Page 154: ...154 Alarm and Failure Data ...
Page 155: ...155 Alarm and Failure Data Continued ...
Page 156: ...156 Alarm and Failure Data Continued ...
Page 158: ...158 Compressor State Table ...
Page 159: ...159 Last RECIPStart Status Table ...
Page 172: ...172 ...
Page 173: ......