Temperature Setpoints
The
TEMPERATURE SETPOINTS
menu allows the user to set temperature related setpoints
described in the following sections.
Discharge Temperature Setpoints
Discharge Temperature Setpoints
The
D
ISCHARGE
T
EMPERATURE
S
ETPOINTS
screen allows the operator to set acceptable
ranges for the RECIP discharge temperature
and second discharge temperature (DT2) for 12 &
16 single stage compressors.
.
The following table lists the data entry fields and a description of their purposes.
TERM
DEFINITION
RANGE
HIGH FAILURE
The compressor is failed (stopped) when
the discharge temperature exceeds this value.
32 - 392 DEGF
Discharge Temperature Setpoints Screen
Discharge Temperature Definitions