HART Commissioning
April 2017
HART Commissioning
It is recommended that Hot Backup be reset immediately after repairing or replacing the affected sensor.
See
“Reset Hot Backup: Fast Keys 2-2-4-1-4” on page 76
. After resetting Hot Backup, the DeltaV
Faceplate window indicates the alarms
ADVISE Configuration Change
and
MAINTENANCE Hot Backup Active
.
You must acknowledge these alarms in order to clear them by checking the ACK boxes next to each
alarm.
Yokogawa’s Centum PRM/DTM messages
When the primary sensor fails, alarms will be displayed in the PRM (Plant Resource Manager) via yellow
circles next to the device, as shown below. These yellow circles indicate that something in your process
needs attention. To investigate this further, right click on the affected device, and select
DTM Works…
This will open the DTM (Device Task Manager).