142
Reference Manual
00809-0100-4021, Rev JA
Configuration
April 2017
Configuration
4.5.3
Recommended actions for Plantweb alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that gives a recommended course of
action based on the type and specific event of the Plantweb alerts are active.
Table 4-2. RB.RECOMMENDED_ACTION
Alarm type
Failed/maint/advise
active event
Recommended action
text string
Plan
tw
eb aler
ts
None
None
No action required
Advisory
NV Writes Deferred
Non-volatile writes have been deferred, leave the device
powered until the advisory goes away
Maintenance
Configuration Error
Re-write the Sensor Configuration
Primary Value
Degraded
Confirm the operating range of the applied sensor and/or
verify the sensor connection and device environment
Calibration Error
Retrim the device
Secondary Value
Degraded
Verify the ambient temperature is within operating limits
Failed
Electronics Failure
Replace the Device
HW / SW Incompatible
Verify the Hardware Revision is compatible with the
Software Revision
NV Memory Failure
Reset the device then download the Device Configuration.
Primary Value Failure
Verify the instrument process is within the Sensor range
and/or confirm sensor configuration and wiring.
Secondary Value
Failure
Verify sensor range and/or confirm sensor configuration
and wiring
Diagnostic Error
Sensor Drift Alert or
Hot BU active
Confirm the operating range of the supplied sensor and/or
verify the sensor connection and device environment
Primary Value
Degraded
Confirm the operating range of the supplied sensor and/or
verify the sensor connection and device environment
Summary of Contents for Rosemount 3144P
Page 2: ......
Page 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Page 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...