Simulate switch is used to replace the channel value coming from the sensor transducer block. For
testing purposes, it manually simulates the output of the analog input block to a desired value.
2.4
Mounting
If possible, the transmitter should be mounted at a high point in the conduit run so moisture from the
conduits will not drain into the housing. The terminal compartment could fill with water if the
transmitter is mounted at a low point in the conduit run. In some instances, the installation of a poured
conduit seal, such as the one pictured in
, is advisable. Remove the terminal compartment
cover periodically and inspect the transmitter for moisture and corrosion.
Figure 2-4. Incorrect Conduit Installation
Figure 2-5. Recommended Mounting with Drain Seal
Standard operation (factory default)
NAMUR-compliant operation
Fail high
21.75 mA
≤
I
≤
23.0 mA
Fail high
21 mA
≤
I
≤
23.0 mA
High saturation
I
≥
20.5 mA
High saturation
I
≥
20.5 mA
Low saturation
I
≤
3.90 mA
Low saturation
I
≤
3.8 mA
Fail low
I
≤
3.75 mA
Fail low
I
≤
3.6 mA
A. Sealing compound
B. Union coupling with extension
C. Conduit for field wiring
D. Thermowell
E. Sensor hex
F. Poured conduit seal (where required)
Conduit
lines
Conduit
lines
A
D
B
E
F
C
Summary of Contents for Rosemount 3144P
Page 2: ......
Page 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Page 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...