Configuration
April 2017
Configuration
4.9.3
Filtering
Note
If damping has already been configured in the transducer block, setting a non-zero value for PV_FTIME
will add to that damping.
The filtering feature changes the response time of the device to smooth variations in output readings
caused by rapid changes in input. Adjust the filter time constant (in seconds) using the PV_FTIME
parameter. To disable the filter feature, set the filter time constant to zero.
4.9.4
Process alarms
Process alarm detection is based on the OUT value. Configure the alarm limits of the following standard
alarms:
High (HIGH_LIM)
High high (HIGH_HIGH_LIM)
Low (LOW_LIM)
Low low (LOW_LOW_LIM)
To avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in
percent of the PV span can be set using the ALARM_HYS parameter. The priority of each alarm is set in
the following parameters:
HIGH_PRI
HIGH_HIGH_PRI
LOW_PRI
LOW_LOW_PRI
Alarm priority
Alarms are grouped into five levels of priority.
Priority
number
Priority description
0
The alarm condition is not used.
1
An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
2
An alarm condition with a priority of 2 is reported to the operator.
3–7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
8–15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
Summary of Contents for Rosemount 3144P
Page 2: ......
Page 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Page 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...