153
Reference Manual
00809-0100-4021, Rev JA
Configuration
April 2017
Configuration
AI blocks (basic configuration)
AI1 as process temperature
1. Put the AI Block into OOS mode.
a. Go to
MODE_BLK.TARGET
.
b. Select
OOS (0
80)
.
2. Go to
CHANNEL
.
a. Select
Sensor 1.
3. Go to
L_TYPE
.
a. Select
Direct
.
4. Go to
XD_Scale
.
a. Select
UNITS_INDEX
to be °F.
b. Set 0% = –200, set 100% = 500.
5. Go to
OUT_SCALE
.
a. Select
UNITS_INDEX
to be °F.
b. Set the 0 and 100 scale to be the same as in
.
6. Put the AI block back into auto mode.
7. Follow host procedure to download schedule into block AI2 as terminal temperature (body
temperature).
8. Put the AI block into OOS mode.
a. Go to
MODE_BLK.TARGET
.
b. Select
OOS (0
80)
.
9. Go to
CHANNEL
.
a. Select
Terminal (Body) Temperature
.
10. Go to
L_TYPE
.
a. Select
Direct
.
11. Go to
XD_Scale
.
a. Select
UNITS_INDEX
to be °F.
b. Set 0% = –40, set 100% = 185.
12. Go to
OUT_SCALE
.
a. Select
UNITS_INDEX
to be °F.
b. Set the 0 and 100 scale to be the same as in
.
13. Put the AI block back into Auto mode.
14. Follow host procedure to download schedule into block.