Reference Manual
00809-0100-4021, Rev JA
Configuration
April 2017
Configuration
The following table displays all possible configurations of the WRITE_LOCK parameter.
FEATURES_SEL
FEATURES_SEL turns on any of the supported features. The default setting of the transmitter does not
select any of these features. Choose one of the supported features, if any.
MAX_NOTIFY
The MAX_NOTIFY parameter value is the maximum number of alert reports that the resource can send
without getting a confirmation, corresponding to the amount of buffer space available for alert
messages. The number can be set lower to control alert flooding by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
4.5.2
Plantweb
™
alerts
The alerts and recommended actions should be used in conjunction with
The Resource Block acts as a coordinator for Plantweb alerts. There will be three alarm parameters
(FAILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which contain information regarding some of the
device errors detected by the transmitter software. There will be a
RECOMMENDED_ACTION parameter used to display the recommended action text for the highest
priority alarm and a HEALTH_INDEX parameters (0–100) indicating the overall health of the transmitter.
FAILED_ALARM has the highest priority, followed by MAINT_ALARM, and ADVISE_ALARM is the lowest
priority.
FAILED_ALARMS
A failure alarm indicates the device or some part of the device is non-operational, and the device is in
need of repair. There are five parameters associated with FAILED_ALARMS.
FEATURE_SEL
HW_SEL bit
FEATURE_SEL
SW_SEL bit
SECURITY
SWITCH
WRITE_LOCK
WRITE_LOCK
Read/Write
DEFINE_WRITE_
LOCK
Write access to
blocks
0 (off)
0 (off)
N/A
1 (unlocked)
Read only
N/A
All
0 (off)
1 (on)
N/A
1 (unlocked)
Read/write
N/A
All
0 (off)
1 (on)
N/A
2 (locked)
Read/write
Physical
Function Blocks
only
0 (off)
1 (on)
N/A
2 (locked)
Read/write
Everything
None
1 (on)
0 (off)
(1)
1.
The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit
is set to 1 (on), the SW_SEL bit is automatically set to 0 (off) and is read only.
0
(unlocked)
1 (unlocked)
Read only
N/A
All
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Physical
Function Blocks
only
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Everything
None
Summary of Contents for Rosemount 3144P
Page 2: ......
Page 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Page 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...