HART Commissioning
April 2017
HART Commissioning
5. When prompted, choose which variable you would like as your primary variable (PV) and select
ENTER
. With Hot Backup enabled, the PV must either be
First Good Temperature
or
Average
Temperature
.
Disable Hot Backup in guided setup: Fast Keys 2-1-5
1. From the
Home Screen
, select
2 Configure
.
2. Select
1 Guided Setup
.
3. Select
5 Config Hot Backup
.
4. When prompted, select
1 Yes
to disable Hot Backup. To reconfigure Hot Backup,
select
2 No
.