Specifications and Reference Data
April 2017
Reference Manual
00809-0100-4021, Rev JA
Specifications and Reference Data
200
Standard configuration
Both standard and custom configuration settings may be changed. Unless specified, the transmitter will be shipped as
follows:
Standard configuration
Setting
4 mA value/lower range (HART/4–20 mA) measurement point LO (F
OUNDATION
Fieldbus)
0 °C
20 mA value/upper range (HART/4–20 mA) measurement point HI (F
OUNDATION
Fieldbus)
100 °C
Damping
5 seconds
Output
Linear with temperature
Failure mode (HART/4–20 mA)
High
Line voltage filter
60 Hz
Software tag
If a Hardware Tag is specified it will be
entered into the software tag as well.
Otherwise it will be left blank.
Optional integral display
Units and mA/sensor 1 units
Single-sensor option
Setting
Sensor type
4-wire, Pt 100
α
= 0.00385 RTD
Primary variable (HART/4–20 mA) AI 1400 (F
OUNDATION
Fieldbus)
Sensor 1
Secondary variable AI 1600 (F
OUNDATION
Fieldbus)
Terminal temperature
Tertiary variable
Not used
Quaternary variable
Not used
Dual-sensor option
Setting
Sensor type
Two 3-wire, Pt 100
α
= 0.00385 RTD
Primary variable (HART/4–20 mA) AI 1400 (F
OUNDATION
Fieldbus)
Sensor 1
Secondary variable AI 1500 (F
OUNDATION
Fieldbus)
Sensor 2
Tertiary variable AI 1600 (F
OUNDATION
Fieldbus)
Terminal temperature
Quaternary variable
Not used
Summary of Contents for Rosemount 3144P
Page 2: ......
Page 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Page 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...