HART Commissioning
April 2017
HART Commissioning
Viewing Thermocouple Diagnostic Alerts: Fast Keys 1-1-2
When the Thermocouple Degradation diagnostic detects a degraded sensor, the LCD display will display
a message; “ALARM SNSR 1 FAIL AO”
1. Select
1 Overview
.
2. Select
1 Device Status: Maintenance
.
3. If Sensor 1 has degraded, select
2 M: Sensor 1 Degraded.
If Sensor 2 has degraded, select
2 M: Sensor 2 Degraded.
Resetting Thermocouple Degradation alerts: Fast Keys 1-1-1
1. Select
1 Overview
.