52
Reference Manual
00809-0100-4021, Rev JA
HART Commissioning
April 2017
HART Commissioning
It is recommended Hot Backup be reset immediately after repairing or replacing the affected sensor. See
“Reset Hot Backup: Fast Keys 2-2-4-1-4” on page 76
. After resetting Hot Backup, the Field
Communicator will display an
Advisory
Device Status, indicating that the configuration has changed. This
is shown in the
Overview
section. To clear this advisory, clear the configuration changed flag, as shown
below:
1. Select
1 Device Status
to view the active alerts.
2. Select
2 A: Configuration Changed
.
3. Select
2 Clear Config Changed Flag
.
LCD display message
The LCD display on the transmitter will display a message
HOT BU SNSR 1 FAIL
as well as the output of the
secondary sensor that has taken over the process.