January 2016, Rev. 1
CAM216/16 IOM
Doc. Number: ECM-402-0116
24
Section 3: Installation of CAM216
Installation of CAM216
b.
Connect J5 Jumper in P2P Mode.
Figure 30
J5 Jumper in P2P Mode
P2P
MDROP
CAM16 J5
P2P
MDROP
CAM16 J5
CAM216 J5
MDROP
P2P
CAM216 J5
MDROP
P2P
6.
HART – Digital Control (Multi-Drop; Actuator Must be in Network Control Mode):
It is important to make sure that all devices to be connected in this mode have a
different HART address. The HART polling address can be found under the HART device
information for each device. Make sure that you connect one device at the time while
changing the addresses as to avoid having devices with the same address on the
network. Connect J5 Jumper in Multidrop Mode.
Connection shall be as follows –
Table 18.
HART Control Types (10)
HART(+)
STC Pin 43
HART(-)
STC Pin 44
7.
HART Digital Control (Wireless THUM; Actuator Must be in Network Control Mode):
Refer to Section 12 for details about the THUM wiring and configuration.
8.
Modbus Channel on CAM216:
CAM216 also supports one Modbus channel. Please refer to TEC2000 STC Image and
Pin 39 and 40 would be used for RS 485 connection.
Table 19.
HART Control Types (11)
)
STC Pin 40
MODBUS(-)