January 2016, Rev. 1
CAM216/16 IOM
Doc. Number: ECM-402-0116
18
Section 2: Installation of CAM16
Installation of CAM16
Table 14.
STC Pins
STC Pins
STC Back Pins
CAM card pins
HART Connection
41
5
J4(0+)
HART O+
42
2
J4(0-)
HART O-
43
6
J4(I+)
HART I+
44
3
J4(I-)
HART I-
Figure 21
CAM16 J3 STC Connection
6.
To connect the other end of the wire harness to STC
On the CAM16, locate connector J4 and make sure that it is securely connected to
the inside of the actuator using a 6-wire connector. This connector provides the
communication between the LDM and the STC on the EHO, if missing or not properly
connected; you will not be able to establish communication to your device
The wire harness fits into the 6-pin micro-fit connector on the inner side of the STC.
Temporarily separate the STC from the EHO enclosure by removing 4 bolts, so that it
will be easy to connect the wire harness. Plug the wire harness into the 6-pin housing
connector on the STC's back side and reinstall the STC assembly.