CAM216/16 IOM
Doc. Number: ECM-402-0116
January 2016, Rev. 1
19
Section 2: Installation of CAM16
Installation of CAM16
Figure 22
CAM16 J3 Connection for EHO STC
Remove
screws
to access
backside
of STC
7.
Reassemble the Field Board with connectors.
8.
Reinstall the LDM assembly back to the EHO unit.
9.
Now follow steps 10, 11 or 12 depending on your HART network type.
Table 15.
HART Control Types (8)
Control Type
Steps to Follow
HART - Analog Control (Point to Point)
Step 10
HART - Digital Control (Multi Drop)
Step 11
HART - Digital Control (Wireless THUM)
Step12
10.
HART – Analog Control (Point to Point; Actuator Must be in Analog Control Mode)
a.
Connect the HART 4-20 mA signal to the STC Pin 43 and 44. The 4–20 mA
output would be available at STC Pin 41 and 42. These output pins must be
connected to the actuator’s analog input 1 STC Pin 25 and 26.
b.
Connect Jumper J5 in P2P
Figure 23
CAM16 J5 Jumper
J5