CAM216/16 IOM
Doc. Number: ECM-402-0116
January 2016, Rev. 1
23
Section 3: Installation of CAM216
Installation of CAM216
3.
On the CAM216, locate connector J6 and make sure that it is securely connected
to the inside of the actuator using a 6-wire connector. This connector provides the
communication between the ACM and the STC on the TEC2000, if missing or not
properly connected, you will not be able to establish communication to your device.
Figure 29
TEC2000 Sealed Terminal Chamber Pin Diagram
4 - 20 mA Input
with HART
[ 43 ( HART - )
and 44 (HART + ) ]
Connect pin 25
to pin 41
Connect pin 26
to pin 42
4.
Now that the CAM216 is in place, close and bolt down the ACM chamber. Then, locate
the Separate Terminal Chamber (STC) on the back of the TEC2000. Then, follow step 5,
6 or 7 depending on your HART Network type:
Table 17.
HART Control Types (9)
Control Type
Step to Follow
HART – Analog Control (Point-to-Point)
Step 5
HART – Digital Control (Multi-Drop)
Step 6
HART – Digital Control (Wireless THUM)
Step 7
5.
HART Analog Control (Point-to-Point; Actuator Must be in Analog Control Mode):
a.
Connect the HART 4-20 mA signal to the STC Pin 43 and 44. The 4–20 mA
output would be available at STC Pin 41 and 42. These output pins must be
connected to the Actuator’s Analog Input 1 STC Pin 25 and 26.