CAM216/16 IOM
Doc. Number: ECM-402-0116
January 2016, Rev. 1
21
Section 3: Installation of CAM216
Installation of CAM216
Section 3: Installation of CAM216
Emerson Process electric actuators equipped with HART CAM216 option require a main power
source. This source will power the electric motor and all electronic controls including the
CAM216. The CAM216 HART interface is powered directly from the device, and is not capable
of communication when the actuator does not have power. Refer to the site planning guide
for proper wire types, termination, length, and others into an Emerson Process Management
electric actuator.
The CAM216 is supported by the TEC2000, TEC2 and Model 500 electric actuators equipped
with Auxiliary Control Module (ACM) and proper wiring. For more information about installing
the ACM, refer to TEC2000 Installation and Operation Manual E2K-405-0703.
Figure 25
CAM216
3.1
Installation of HART CAM216 in TEC2000 Unit
1.
Remove power from the device and open the frontal side chamber on the TEC2000 by
removing the 4 bolts located on each corner. After removing the bolts, pull the side
chamber outwards to gain access to the ACM. If it is difficult to remove, you might
assist the removal of the chamber by driving in the removed bolts on the threaded
corner openings to help the cover “push” itself out as you drive in the bolts.