January 2016, Rev. 1
CAM216/16 IOM
Doc. Number: ECM-402-0116
28
Section 4: HART Quick Setup and Actuator Options
HART Quick Setup and Actuator Options
1.
Place the Selector Knob in OFF, then; move the control knob in the following order
within 3 seconds: open, close, open, close, open, and close. If done correctly, “Setup?”
will appear on screen.
2.
By Moving the Control Knob, navigate to Setup -> Display Unit Parameters -> Control
Mode and verify that “Network” or “Analog” is selected as required. Select “Next” and
verify that “Network Adapter” shows “HART Block” or “HART Modulation” mode.
3.
Make sure the Network “Response Delay” parameter; set to 8 mSecs.
4.
Place the Selector Knob in BACK and wait until it reaches to “Setup?” then move the
Control Knob to “NO” and you will be exited from the Setup Mode.