January 2016, Rev. 1
CAM216/16 IOM
Doc. Number: ECM-402-0116
8
Section 2: Installation of CAM16
Installation of CAM16
b.
Select the Jumper J5 in P2P Mode.
Figure 4
Jumper J5 Location
P2P
MDROP
CAM16 J5
P2P
MDROP
CAM16 J5
CAM216 J5
MDROP
P2P
CAM216 J5
MDROP
P2P
c.
For Analog mode, CAM16 – Connector J4, Pin 1 and 2 (CAM CARD 4 – 20 mA
Output) should be connected to Pin 1 and Pin 2 (Analog Input 1) of Connector
P1 of 320 B Board.
d.
Ensure that all connections from step 5 are properly secured among CAM16,
320B board and the HART Input signal. Then, tighten the screws and proceed
to close the unit.
6.
HART Digital Control (Multi-Drop)
a.
Connect the HART Analog 4 – 20 mA input signal as follows:
Table 8.
HART Control Types (3)
HART (+)
Connector J4, PIN 3
HART (-)
Connector J4, PIN 4
b.
Select the Jumper J5 in Multi-Drop Mode.
Figure 5
Jumper J5 in Multi-Drop Mode
P2P
MDROP
CAM16 J5
P2P
MDROP
CAM16 J5
CAM216 J5
MDROP
P2P
CAM216 J5
MDROP
P2P
c.
Do the necessary changes in Host. It is important to make sure that all devices
to be connected in this mode have a different HART address. The HART
polling address can be found under the HART device information for each
device. Make sure that you connect one device at the time while changing the
addresses to avoid having devices with the same address on the network.