Introduction
•
Auxiliary Digital Inputs
Quantity and Type – Two, Independent opto-isolated with high-side and
low-side sensing
Voltage – 10-30 VDC
Current – 4 mA maximum turn-off, 10 mA minimum turn-on, 12 mA typical at 24 VDC
•
Auxiliary Analog Inputs
Two, 4-20 mA (24 VDC power available from actuator to power all auxiliary I/O)
•
Optional Analog Output
(Option must be specified at Time of Order)