CAM216/16 IOM
Doc. Number: ECM-402-0116
January 2016, Rev. 1
27
Section 4: HART Quick Setup and Actuator Options
HART Quick Setup and Actuator Options
1.
Setup Mode Display Sequence:
The three (3) amber LED’s for the LOR section flash to indicate Setup Mode. When
in setup mode, the user must enter the REMOTE(NEXT) or LOCAL(BACK) within 120
seconds or the display will revert back to the normal display mode.
Setup data may be changed by using the UP and Down entries of the Control Knob.
The UP and Down entries are active only after a valid pass-code is entered and the
Selector Switch is in the STOP position. The default pass-code is P1 00 and P2 00. Once
the correct pass code is entered and accepted at the actuator controls, the user will
then be able to advance through the displays shown in the Main Menu table:
Table 20.
Main Menu Table
Menu
Parameter
Value
Units
Default
C0
Control Mode
0-1
0=Discrete
1=Network
1
—
The table on the following page shows the sequence of the setup menus. It
also shows the selections, units, and defaults. Each time the REMOTE (NEXT)
selector knob is selected, the display advances to the next menu item. Each
time the LOCAL (BACK) selector knob is selected, the display backs up to the
previous menu item. The UP and DOWN control knob is used to increment or
decrement the value shown in the table.
Once in setup mode, navigate through the menus and verify that the proper
setup is configured.
NOTE:
RDM port configuration is fixed at 9600 Baud rate, None Parity Bit, 8 Data Bits, 1 Stop Bit
and Network Address 254 and may not be changed by the user. Only the network port
configuration may be changed. The address programmed for the network port will be
accepted by the RDM port in addition to address 254.
4.4
TEC2000, TEC2 and Model 500 Quick Setup
Instructions
The TEC2000 is factory configured as specified by the customer purchase order. If field
setup or factory configuration changes are required, contact your nearest Emerson Process
Management representative for assistance. Only authorized Emerson Process Management
Representative or trusted partner should make modification to factory settings. Operating
modes for the TEC2000 may be reviewed by using DCMlink software or by navigating on the
LDM Setup menu. As a minimum, the Network Adapter must be set for HART (On/Off) (Block)
mode or the HART Positioner (Analog) (Modulating) mode. Valve Position Feedback must be
calibrated for either device type by stroking the valve from the CLOSE to OPEN and OPEN to
CLOSE limits with selector switch in the LOCAL mode.
You can set or verify the following information by setting up DCMlink on the device or by
navigating on the LDM Setup menu.
Setup through LDM:
First, locate the Selector knob (Local, off, remote) and the control knob (Open, Close) on the
front of the LDM. You will use the Control knob to answer “yes” or “no” at prompts on screen
during setup. You will use the selector knob to navigate “back” or “next” through the menu
options.