Section 2: Installation of CAM16
Installation of CAM16
11.
HART – Digital Control (Multi-Drop)
Table 16.
HART Control Types (9)
HART Connection
Pins
HART (+)
STC Pin 43
HART (-)
STC Pin 44
a.
It is important to make sure that all devices to be connected in this mode have
a different information for each device. Make sure that you connect one device
at a time while changing the addresses as to avoid having devices with the
same address on the network.
b.
Connect J5 Jumper in Multidrop Mode
Figure 24
CAM16 J5 Configured for Multidrop Mode
P2P
MDROP
CAM16 J5
P2P
MDROP
CAM16 J5
CAM216 J5
MDROP
P2P
CAM216 J5
MDROP
P2P
12.
HART – Digital Control (Wireless THUM)
Refer to
Section 12
for details about the THUM wiring and configuration.
13.
Switch ON the power to the unit.
14.
Through LDM Menu;
a.
Set Control Mode(CO) to 7 (Network)
b.
Set the Network Adapter Parameter (nA) to 9 (HART Block Mode) or 10 (HART
Modulation Mode) (Refer LDM Flow document for navigation)
15.
Save the settings