DL8000 Preset Instruction Manual
Revised February-2016
Modules
3-3
Table 3-1. 12 Volt DC Power Input Terminal Block Connections
Terminal Blocks
Definition
Volts DC
BAT+ and BAT–
Accepts 12 Volts dc nominal from an
AC/DC converter or other 12 Volt dc
supply.
Absolute Maximum: 11.25 to 16 Volts dc
Recommended Operating Range: 11.25 to
14.25 Volts dc
CHG+ and CHG–
Analog Input used to monitor an external
charging source.
0 to 18 Volts dc
AUX+ and AUX–
Supplies reverse-polarity-protected
source voltage to external devices.
BAT+ minus
∼
0.7 Volts dc
AUX
SW
+ and
AUX
SW
–
Supplies switched power for external
devices.
0 to 14.25 Volts dc
Table 3-2. 12 Volt DC Power Input LED Fault Indicators
Signal
LED
V
OK
Green LED on when voltage is in tolerance on BAT+ and BAT–.
V
OFF
Fault – Red LED on when the AUX
SW
+ output are disabled by the CPU control line.
V
OVER
Fault – Red LED on when AUX
SW
+ is disabled due to excess voltage on BAT+.
TEMP
Fault – Red LED on when AUX
SW
+ output are disabled due to the excess temperature of the Power
Input module.
3.2 Input/Output Modules
The I/O modules typically consist of a terminal block for field wiring
and connectors to the backplane. The DL8000 supports up to nine I/O
modules, and can accommodate a wide range of process inputs and
outputs. Each I/O module electrically connects to field wiring by a
removable terminal block. Refer to
Figures 3-2
and
3-3
.
DOC0513A
Front View
Side View
Figure 3-2. Typical I/O Module