DL8000 Preset Instruction Manual
Revised February-2016
Communications Protocols
D-21
Prompt Preset
Volume
[0x08]
Results
When an operator enters the preset value, the
DL8000 sets the Preset Volume Entered flag (bit 6
in [63,0,119]). A Prompt Preset Volume [0x08]
command, Authorize Batch [0x0A] command, or a
Clear Status [0x13] command clears this flag.
After this the DL8000 displays the messages
“Please Wait” and either “Preset Entered” or
"Timeout Operation" (depending on the time out
activity) and waits for a command. The TAS can
read preset volume entered [63,0,39] using
Modbus read function code.
Authorize Batch
[0x0A]
Authorizes the batch for given preset volume [63,0,39]. When the batch
authorizes, the DL8000 displays a loading screen. This also increments the
batch sequence number [63,0,125] by
1
(which may roll from 9999 to 0) to
indicate the prospective sequence number if the batch starts.
The operator must start loading within the timeout time [63,0,171]; otherwise
the system sets the Operation Timed Out flag and automatically aborts the
batch.
Flags Immediately Set
K&D Locked Out
Batch Authorized
Flags Immediately
Cleared
Preset Volume Entered
Operation Timed Out
Batch Ended
Batch Aborted
Batch Stopped
Batch in Progress
Exceptions
Passcode Entry in Progress
Primary Alarm active
Batch Authorized
No transaction authorized
Operating Mode is Manual
K&D Locked Out
Invalid preset volume
Maximum batches delivered for transaction
Maximum Transaction Total (0x5F)
Tolerance error (0x5B)
Flow Rate Too Low/High
Supporting
Parameters
Preset Volume Entered [63,0,39]
Timeout time [63,0,171]