DL8000 Preset Instruction Manual
Revised February-2016
DL8000 Keypad Display
E-55
Once the calibration completes, the program displays a summary screen.
You can then accept or reject the new calibration value(s):
14/03/12 12:26:02
Enter ZERO EU
Enter SPAN EU
(ENTER to accept )
Live Dead
-0.09100 0
99.857282 100
(STOP to Reject )
When you press
ENTER
, the program updates the values and displays a
screen indicating the successful completion of the calibration process.
14/03/12 12:26:02
Calibration Done
The program then redisplays the channel selection screen. You can
begin another AI calibration or exit the AI calibration menu.
If you press
STOP
, the program restores the old calibration values.
Affected
Point Types
The program affects the following point types during calibration:
ZERO EU [103,X,13]
MID point 1 [103,X,14]
MID point 2 [103,X,15]
MID point 3 [103 X,16]
SPAN EU [103,X,17]
Set value [103,X,19]
Calibration mode [103,X,34]
Calibration type [103,X,35]
E.4.3 Calibrating RTDs
Note
:
The preset must have an installed RTD module to calibrate
RTDs. If you attempt an RTD calibration without a module, the
system displays the message
NO RTD Card in system
on the left-
hand screen.
To calibrate RTDs, select the
RTD
Calib
option on the Calibration
menu screen: