DL8000 Preset Instruction Manual
3-8
Modules
Revised February-2016
If required, you can calibrate the low end of the analog signal to zero
(refer to
Chapter 7
in the
ROCLINK 800 Configuration Software User
Manual)
(
for DL8000) (part D301259X012).
Note
:
The AI-16 module provides 16-bit resolution and uses a 24-bit
A/D converter. DIP switches on the AI-16 control the scaling
(see
Figure 3-6
).
You can configure the AI (+T) as either 12 or 24 Volts dc using jumper
J4 on the AI-12 module (see
Figure 3-4
). The AI modules can provide
is12 Volts dc or +24 Volts dc field transmitter power on a per
module basis. For example, one module can p12 Volts dc for
powering low-power analog transmitters, while another module in the
same DL8000 controller can p24 Volts dc for powering
conventional 4 to 20 mA transmitters. See
Figure 3-5
.
Figure 3-4. AI-12 Jumper J4 (Shown Set to +12V)
1-5 VOLT DEVICE
EXTERNALLY POWERED
+
-
1-5 VOLT DEVICE
EXTERNALLY POWERED
+
-
ROC809 POWERED
CURRENT LOOP DEVICE 4-20mA
-
+
OUT SIGNAL
COM
IN
DOC0506A
Figure 3-5. Analog Input Module Field Wiring
Precision
Resistor
+T 12 / 24 V dc
Jumper