DL8000 Preset Instruction Manual
E-100
DL8000 Keypad Display
Revised February-2016
14/03/12 12:26:02
Set Port
Rx Bytes / Tx Bytes
Baud rates
Par/StopBit/DataBit
Diag. in progress…
Please Wait…
RS485 ch 4
120/120
PPPPPPPPP
The system also tests parity bits, stop bits, and data bits, again using
P
to indicate a successful test and
F
to indicate a failure. When the test
completes the message
STOP to End
appears at the bottom of the
screen:
14/03/12 12:26:02
Set Port
Rx Bytes / Tx Bytes
Baud rates
Par/StopBit/DataBit
(STOP to End )
RS485 ch 4
120/120
PPPPPPPPP
PPP
Press
STOP
to end the test and return to the comm port selection
screen. Press
EXIT
to display the Diagnostics main menu.
E.5.8 Error Messages
Table
E-11
lists error messages that could appear on the DL8000
display.
Table E-11. Error Messages
Message
Description
Archive Config Err
Transaction or batch configuration error
Blend Toler. Fail
Preset verification failed; component percentages
are out of allowed tolerance limit
Btch/Trans Lmt Cros
Preset verification failed; limit on batches per
transaction exceeded.
Invd Additive
Additive verification failed
Inv Adtv type
Recipe verification failed; invalid additive type
Invd Comp Ratio
Recipe verification failed; invalid component ratio
in selected recipe
Invd Delivery Seq
Recipe verification failed; invalid delivery
sequence
Invd Meter
Recipe verification failed; invalid meter
assignment
Invd Driver
Invalid driver ID entered
Invd Prset Adtv op
Recipe verification failed; invalid additive preset
option