DL8000 Preset Instruction Manual
Revised February-2016
DL8000 Keypad Display
E-31
SYSTEM Menu
Alarm, Process Alarm
(1 logical, point type 63)
Headings (Submenu Page 1)
TLP
Min Comp Temp
63,0,157
Max Comp Temp
63,0,158
Min Comp Dens
63,0,163
Max Comp Dens
63,0,164
Min Comp Press
63,0,160
Max Comp Press
63,0,161
Headings (Submenu Page 2)
TLP
Max perm Temp drft
63,0,225
Temp Fail Alm Act
63,0,181
Off
Display
Stop Batch
Close Contact
Lock Unit
Press Fail Alm Act
63,0,182
Off
Display
Stop Batch
Close Contact
Lock Unit
Dens Fail Alm Act
63,0,183
Off
Display
Stop Batch
Close Contact
Lock Unit
Temp drift Alm act
63,0,224
Off
Display
Stop Batch
Close Contact
Lock Unit
Alarm, System Alarm
(1 logical, point types 63 & 64)
Headings (Submenu Page 1)
TLP
Storage Mem Alm %
64,0,0
Max Allwd Dev Temp
63,0,229
ParamResAlmResTime
63,0,207
System Alm Act
63,0,146
Off
Display
Stop Batch
Close Contact
Lock Unit
IntlTempFailAlmAct
63,0,227
Off
Display
Stop Batch
Close Contact
Lock Unit
KD Comm Fail Alm
64,0,42
Off
Display
Stop Batch
Close Contact
Lock Unit
Headings (Submenu Page 2)
TLP
Power Fail Alm Act
63,0,56
Off
Display
Stop Batch
Close Contact
Lock Unit