3 Installation
3.4 Power bus
92
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
3.4.1.2 End-pieces and lead-throughs
Once the flexible busbar has been routed, all free busbar ends must be safely
terminated and sealed as required to achieve protection class IP65. To do this,
use cable end pieces (RA-C1-END1) and bushings (RA-C1-DF) as necessary.
Figure 49:
RA-C1-DF bushing for ribbon cable
The flexible busbar can be fed into distribution module RA-C1-VM-7 or a
control panel using an RA-C1-DF bushing.
▶
Cut the cable to the desired dimension.
Figure 50:
RA-C1-CUT
Hand tool for cutting ribbon cables
▶
Strip the flexible busbar to the required length:
•
For a ribbon cable end piece, strip 19 mm,
•
for distributor module to 50 mm,
•
for control panel as required.
Figure 51:
RA-C1-AZ-4
Tool for stripping the cable sheath
→
For cutting to length we recommend tool RA-C1-CUT.
→
Tool RA-C1-AZ-4 is recommended for stripping 7 x 4 mm
2
flexible bus bar.
When using a standard cable stripper, do not cut into the rubber
sheath by more than 0.7 mm in order to avoid damaging the
insulation of the conductor.