
5 RAMO5 motor starter
5.7 Configure specialist settings
130
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
5.7.2 Set the rated motor current (P1-08)
Before commissioning the RAMO5 motor starter, the current monitor must
be set to the rated motor current (using parameter P1-08).
Figure 80:
Set rated motor current
Table 23:
Parameter P1-08
ATTENTION
Parameter P1-08 can only be changed if the key switch is in the
OFF/RESET position.
Switching the key switch during operation may cause the motor
to start up accidentally.
Parameter
Description
Unit
Value range
P1-08
Nominal motor current
A
0.3 - 6.6
1410 mi n
230/400 V
3.2/1.9 A
50 Hz
-1
1,1KW
cos ϕ 0.79
P1-08