6 RASP5 speed controller
6.7 Configuration of specific settings
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
153
6.7.7 Stop behavior
RASP5 units do not require an external 24 V DC control voltage.
However, via the AS-Interface connection, RASP5 offers the option of using
the second ramp (P2-13) to bring the motor to a controlled stop when the
external 24 V DC voltage is removed. For this purpose, this 24 V DC voltage
must be fed in using the M12
AS-Interface connector.
Figure 93:
Example of a 24 V DC power connection
→
The following description of the stop behavior applies only to
the RASP5-xxxxA… variants
Parameter
Designation
Description
Unit
Min
Max
DS
P3-11
t-dec Select B0
Deceleration ramp selection - bit 0
External stop function:
0: deactivated
1: activated
–
0
1
0
→
The second deceleration time can be set using the parameter
P2-13.