9 Communication
9.1 AS-Interface
200
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
9.1.13 Controlling RASP5 via the AS-Interface
Table 50:
Controlling RASP5
•
The START signal or enable for the requested operating direction is
issued through DQ0 (FWD) or DQ1 (REV).
•
The fixed frequencies f-Fix1 to f-Fix4 (digital setpoint value memory) are
called up in binary code through outputs DQ2 and DQ3.
•
If DQ2 and DQ3 are not activated, the frequency set in f-Fix1 is issued.
Function
Signal to RASP5
Outputs
Inputs
DQ0
DQ1
DQ2
DQ3
DI0
DI1
DI2
DI3
No controller enable
0
0
Anticlockwise rotating field (REV)
0
1
Clockwise rotating field (FWD)
1
0
No controller enable/reset
1
1
f-Fix1 (P1-12 = 10 Hz)
0
0
f-Fix2 (P2-01 = 30 Hz)
1
0
f-Fix3 (P2-02 = 40 Hz)
0
1
f-Fix4 (P2-03 = 50 Hz)
1
1
Automatic mode
1
No automatic mode
0
Accumulative error
0
No accumulative error
1
External input SEN I1
no signal
0
Signal available
1
External input SEN I2
no signal
0
Signal available
1