6 RASP5 speed controller
6.4 Specific technical data
138
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
6.4 Specific technical data
The following tables show the technical data of the RASP5 speed controller
in the individual power classes with the assigned motor power.
→
The motor power allocation is based on the rated operational
current.
→
The motor power indicates the respective active power output
to the drive shaft of a normal, four pole, internally or externally
ventilated three-phase asynchronous motor with 1500 rpm
(at 50 Hz) and 1800 rpm (at 60 Hz).
Symbol
Unit
RASP5-2…
RASP5-4…
RASP5-5…
RASP5-8…
Rated current (I
e
)
I
e
A
2.4
4.3
5.6
8.5
Overload current for 60 s every
600 s at 40 °C
I
L
A
3.6
6.5
8.4
12.75
Startup current for 2 s
every 20 s at 40 °C
I
L
A
4.8
8.6
11.2
17
Apparent power at 400 V rated
operation
S
kVA
1.84
3.27
4.24
6.49
Assigned motor power at 440 V,
60 Hz
P
kW
0.75
1.5
2.2
4
P
HP
1
2
3
5
Setting range
current limitation (P1-08)
l
2
A
0.2 - 2.4
0.4 - 4.3
0.5 - 5.6
0.8 - 8.5
Power supply side (primary side)
Number of phases
3
3
3
3
Rated voltage
U
LN
V
380 V - 15 % - 480 V + 10 %, 50/60 Hz
(380 - 480 V ±0 %, 45 - 66 Hz ±0 %)
Input current
I
LN
A
2.5
4.1
5.3
7.8
Braking
Braking value
I/I
e
%
≦
30
≦
30
≦
30
≦
30
Switch-on threshold for the
braking transistor
U
DC
V DC
765
765
765